Thermal Optimization in Data Centers: Delta T and Containment Strategies

Optimización térmica en data center

Within the intricate web of technology, Data Centers (DCs) stand as essential pillars for data processing. The efficiency of these centers depends intrinsically on thermal management, where the key concept is Delta T.

Understanding Delta T in the World of DCs

In the mathematical and physical language underlying the technological universe, Delta T, denoted as ΔT, emerges as the measure indicating the temperature difference between two points or environments. In the context of DCs, this term becomes the cornerstone for evaluating thermal management efficiency of Information Technology (IT) equipment and the associated cooling infrastructure.

Technical Significance of Delta T in DCs

Technically, Delta T in a DC is calculated by subtracting the temperature of the hot air exiting IT equipment (such as servers) from the temperature of the cold air supplied to these devices. A higher Delta T suggests greater efficiency in the cooling system by absorbing more heat, while a lower Delta T could indicate a decrease in the effectiveness of this critical system.

Critical Importance of Delta T in DCs

Maintaining an appropriate Delta T is essential to ensure that IT equipment operates within recommended temperature limits. Excessive heat can negatively impact the performance and lifespan of electronic components, while an excessively high Delta T could result in unnecessary energy consumption during the cooling process.

Breakdown of the Four Delta T in DCs

Within the intricate thermal framework of a DC, four distinct Delta T values are identified, each with its specific role:

  1. Delta T1 (ΔT1): The temperature difference between the air entering and exiting the cooling unit.
  2. Delta T2 (ΔT2): The temperature differential between the air leaving the cooling unit and entering the servers or IT equipment.
  3. Delta T3 (ΔT3): The temperature variation between the air entering the servers and leaving them.
  4. Delta T4 (ΔT4): The thermal difference between the air leaving the servers and entering the cooling unit.

Optimal Values and Mathematical Formulas for Efficiency

Optimizing the performance of cooling units focuses on specific values. For example, the ideal Delta T1 ranges between 9°C and 12°C, indicating efficient airflow. The mathematical formula ΔT = 3.1W ÷ CFM establishes the relationship between airflow and Delta T, where 3.1 is the constant coefficient at sea level, W is the watts, and CFM is the airflow in cubic feet per minute. Delta T2 and Delta T4 values are ideally close to zero, while Delta T3 generally falls between 10°C and 15°C (20°F to 30°F).

Containment Strategies: The Key to Continuous Efficiency

To maintain these optimal values, hot and cold aisle containment emerges as a critical strategy. Without this measure, issues like air recirculation, low Delta T, and potential hotspots may arise, negatively impacting efficiency and energy consumption. An example of a DC without containment clearly illustrates these problems, highlighting the imperative need to address them.

Practical Implementation: Hot Aisle Containment

The solution to these challenges lies in implementing hot and/or cold aisle containment. This approach, supported by Computational Fluid Dynamics (CFD) analysis, ensures no mixing of airs of different temperatures, thereby improving Delta T values and optimizing the performance of cooling units. A specific example illustrates the application of hot aisle containment, emphasizing its effectiveness in separating airflow based on temperature.

Source: NDC Solutions

Energy Savings and Industry Best Practices

Following industry best practices, the US General Services Administration (GSA) asserts that 4% to 5% of energy costs can be saved for every degree increase in the temperature of the air entering servers or IT equipment. In line with ASHRAE guidelines, the maximum temperature can be up to 27°C (80.6°F), highlighting the feasibility of raising the operating temperature of the DC through aisle containment strategies.

Additional Recommendations for DC Efficiency

Complementing aisle containment strategy, additional recommendations include cabinet covers, LED lighting, preference for white cabinets, eliminating air leaks, and exercising caution by powering off unused servers and IT equipment.

Additional Note: When implementing cold aisle containment, it is imperative to ensure that the fire suppression system agent can reach all areas of the DC. Also, consideration must be given to the fact that the temperature in the hot aisle may become unbearable for technical and operational staff, requiring additional measures to ensure their well-being.

Collaboration with NDC Solutions: Insights into Modular DCs (MDC)

It is crucial to emphasize that these strategies and principles are especially applicable to Modular Data Centers (MDCs). Thermal optimization becomes even more critical in modular environments where space and energy efficiency are priorities. Collaboration with NDC Solutions has enriched this analysis with their specific expertise in Delta T in MDCs, providing valuable insights to maximize efficiency in these environments.

In conclusion, Delta T and aisle containment strategies emerge as crucial elements in the thermal optimization of DCs, especially in modular environments like Modular Data Centers (MDCs). With a technical and professional approach, a perfect balance between operational efficiency, energy savings, and outstanding performance can be achieved in the dynamic world of technology.